ETCI TC6 - Potentially Explosive Atmospheres:
Introduction: || back to top

ETCI's Technical Committee 6 (Equipment for Potentially Explosive Atmospheres) has prepared the National Rules for Potentially Explosive Atmospheres,
ET105:2011. This publication specifies the requirements for electrical installations in potentially explosive atmospheres. This Edition now replaces
the Second Edition and has been in place since 3rd January 2012.
ET105:2011 is available for purchase from ETCI Offices. Please visit ETCI's online store.
Reference should also be made to the National Rules for Electrical Installations (ET101:2008) and the associated legal requirements of the Safety,
Health and Welfare at Work (General Application) Regulations (S.I.299 of 2007), specifically Parts 3 and 8.
In parallel with the development of ET105:2011, TC6 has also undertaken a complete revision of the Sub-System Completion Certificates and Test Records
for Electrical Installations in Potentially Explosive Atmospheres,these are further referenced below.
Please reference ET105:2011 for specific details associated with the testing and documentation requirements for compilation of the Sub-System
Completion Certificate for Potentially Explosive Atmospheres. The attachments below are available for free download, however Page 1 of 4 of the
Sub-System Completion Certificate must be purchased separately as this identifies the unique certification number.
back to top
Sub-System Completion Certificate: || back to top

 |
PDF Format: To view, download or print a pdf document you will need the Adobe Acrobat
Reader plug-in installed on your computer. You may download the reader by clicking on the Get Acrobat Reader image. |
back to top
Additional References: || back to top
back to top
Useful Tools: || back to top
back to top
Frequently Asked Questions: || back to top
Question 1:
What is an "EC Type Examination Certificate"?
Answer 1:
An EC Type Examination Certificate is needed to demonstrate that equipment can be safely operated in a potentially
explosive atmosphere created by the presence of flammable gas, vapour, mist or clouds of combustibe dust. EC Type
Examination Certificates are issued only by European Notified Certification Bodies, such as PTB in Germany, CESI
in Italy, BASEEFA in the UK and many others. The EC Type Examination Certificate is issued following the examination
of the equipment Technical File and testing, according to the relevant standards that are applicable for each
specific type of explosion protection applied to the equipment, such as flameproof or dust proof containers,
intrinsically safe devices, etc. Once the EC Type Examination Certificate is obtained the manufacturer must also
get from a Notified Body a certification of the production: it is a control of the manufacturing activities based
on ISO 9001 and focused on the ATEX requirements of the product. The basis of EC Type Examination Certification is
the European Directive 94/9/EC.
Question 2:
What is 'cold flow' in the context of cables?
Answer 2:
Many types of flame-resistant cable exhibit "cold flow" of the inner sheath bedding, which could have
adverse effects on the protection of the apparatus. Where such cable is used, it is a requirement of I.S.EN 60079-14
clause 9-1-3 to employ a suitable cable entry device. The code of practice clearly states that "a cable gland
employing a compression (displacement) seal should not be used on cable exhibiting cold flow characteristics".
"Cold flow" can be more fully described as thermoplastic materials which flow when subjected to pressure at ambient
temperature, i.e. the inner sheath bedding material will flow away from any pressure applied to it, including that
of a cable gland inner seal of the compression or displacement type, the effect being that there may no longer be
an effective seal on the inner sheath of the cable.
Question 3:
Is the entry thread classed as part of the flame path when a cable gland is fitted to an Exd enclosure?
Answer 3:
The entry thread does form part of the flame path between the enclosure and the cable gland and must,
when installed with parrallel threads, provide at least five full threads engaged between the box and gland.
Question 4:
Does it breach certification if multiple reducers are used on EExe cable glands into a junction
box?
Answer 4:
With regard to an Exe application there is nothing that prevents the use of two adapters. It is not
good practice as cable glands and adapters are normally tested and certified with only one adapter or reducer
fitted from an impact point of view, therefore if you have two you are increasing the effects of the impact and the
number of sealing faces. If the application was flameproof this would not be acceptable.
Question 5:
How should Earth tags be used on/with cable glands/junction boxes in order to ensure correct wiring?
Answer 5:
Earth tags are used where equipotential bonding or earthing of equipment needs to be conducted at a
common earth point outside the enclosure. The way they are used is that they are generally fitted to the front
entry thread of a Cable Gland between the Enclosure and Cable Gland. The tag then has a hole in it into which a
earth screw can be fitted and an earth wire attached, this can then be taken to a common earth point to enable
equipotential bonding. The standard covering earthing in hazardous areas is I.S.EN 60079 14. If a Sealing Washer
is required in addition to the Earth tag this is normally placed between the Enclosure and the Earth tag.
Question 6:
Can a flameproof cable gland be used in an increased safety installation?
Answer 6:
The arrangement of using a flameproof "Exd" cable gland in place of an increased safety "Exe" cable
gland is usually acceptable. You must refer to I.S.EN 60079-14. It is therefore advisable to obtain clearance from
the project/site inspecting authority in advance.
Question 7:
Can an I.P. washer be fitted with an Exd cable gland?
Answer 7:
I.P. washers can be used in Exd applications providing it does not result in the length/number of threads being
less than the standard requirements i.e. 5 full metric threads and 8mm of thread length. Refer to
I.S.EN IEC 6007914.
Question 8:
What modifications can and can΄t be carried out on Exd enclosures?
Answer 8:
Modifications are not permitted on EExd enclosures, i.e. No additional entries, or changes to the
flamepaths etc. If lid screws are lost or damaged, the enclosure manufacturer should be consulted to ensure the
correct screw is sourced as a replacement.
Question 9:
Why are serrated washers used?
Answer 9:
Serrated washers are used to prevent rotation of the earth tag and any loosening of the gland,
locknut/box assembly due to vibration. They are often used on increased safety plastic boxes containing earth
plates which have been site drilled. The washer can also be used to replace the earth plate anti-rotation pips
which are often removed during the machining process.
Question 10:
What are the restrictions on obstructions near flanges of Exd flameproof enclosures?
Answer 10:
- Gas group IIC Minimum of 40mm
- Gas group IIB Minimum of 30mm
- Gas group IIA Minimum of 10mm
Question 11:
What does the X' Suffix On an ATEX Certificate number mean?
Answer 11:
Some products carry a suffix X after the certificate number. This denotes "special certification
conditions". These are given on the certificate and on the installation leaflet. The conditions usually relate to
cable entry, operation, lamps, installation position and location or maintenance, and must be observed by the user.
Question 12:
What does the U' Suffix On an ATEX Certificate number mean?
Answer 12:
Some products carry a suffix U after the certificate number. This denotes "that this is a component
and has a schedule of limitations". These are given on the certificate and on the installation leaflet. The schedule
of limitations must be observed by the user.
Question 13:
What documentation should I receive from a manufacturer/supplier of ATEX equipment?
Answer 13:
Manufacturers/suppliers of ATEX equipment are obliged to deliver a copy of the Declaration of Conformity, a set of
instructions for safe use relating to the product and an "EC Type Examination Certificate". Manufacturers are not
obliged to provide a copy of the Technical File. If you dont receive these things then the manufacturer/supplier
is not fulfilling his responsibilities under the ATEX directive.
Question 14:
What is the stance on Spare Parts and Repair of Equipment under the ATEX Directive?
Answer 14:
If you have pre-ATEX equipment then you can supply spare parts for those products in accordance with the original
design. This is repair of equipment and is handled under ATEX 137. The supply of parts for repair of existing
equipment is not covered under ATEX 94/9/EC. If equipment is modified, (i.e. it is changed to operate or achieve
it's purpose differently than the manufacturer had originally intended) whether it is pre-ATEX or not, may cause it
to require re-assessment, depending on whether the modifications are 'substantial'. This would be the case if the
modifications affect a principle part of the explosion protection. For example, modifying a shaft on a rotating
machine may not be a problem, but modifying an endshield to give different flamepaths would require re-assessment.
If an item of pre-ATEX equipment is to be replaced (because it is no longer able to function or is beyond repair)
then it can be replaced with an equivalent ATEX compliant product. Alternatively it could be replaced with an
identical pre-ATEX certified product, provided that product had been placed on the EU market for use in hazardous
areas before 30 June 2003. Fore more information, please see clause 3.1 of the ATEX Directive (the term 'placed on
the market' is defined in the guidelines).
back to top
Send us a query: || back to top
The ETCI Technical Committee for Potentially Explosive Atmospheres (TC6) value your feedback and would welcome
queries and/or suggestions that would best help the Committee develop the needs of the industry and support others
with a clear understanding of the requirements associated with the I.S.EN Standards which are strongly supported by
the National Rules ET105:2011 3rd Edition.
Your feedback will be held in the strictness of confidentiality.
Click here to go to the general ETCI enquiry form
back to top
|